HT breaker vacuum bottle integrity test is performed to ensure the vacuum bottle is free from leaks and can withstand high voltage.
The test is performed using a vacuum pump and a pressure gauge.
The vacuum pump is connected to the breaker's vacuum bottle and the pressure gauge is connected to the pump.
The vacuum pump is turned on and the pressure gauge is monitored for any drop in pressure.
If the pressure drops, it indi...
The trip supervision relay is responsible for monitoring the trip circuit of a protective device and ensuring its proper functioning.
It supervises the trip circuit to detect any faults or abnormalities.
It ensures that the trip circuit is properly energized and ready to operate when needed.
It monitors the continuity and integrity of the trip circuit wiring.
It can provide alarms or indications in case of trip circuit fai...
ELCB and RCCB are both electrical safety devices, but differ in their operating principles.
ELCB detects earth leakage current and operates on the principle of electromagnetic induction.
RCCB detects both earth leakage and residual current and operates on the principle of differential current transformer.
ELCB is less sensitive and slower in operation compared to RCCB.
RCCB is more expensive than ELCB but provides better p...
Tan delta test is a diagnostic test to measure the quality of insulation in electrical equipment.
It measures the dissipation factor of insulation material
It helps to detect any defects or deterioration in the insulation
It is commonly used for testing transformers, cables, and capacitors
The test involves applying a voltage to the equipment and measuring the current and phase angle
A high tan delta value indicates poor in
There are several types of motor testing including insulation resistance, winding resistance, and vibration analysis.
Insulation resistance testing measures the resistance of the insulation material surrounding the motor windings.
Winding resistance testing measures the resistance of the motor windings themselves.
Vibration analysis testing measures the level of vibration in the motor to detect any potential issues.
Other ...
PI test is a method to measure the insulation resistance of the motor winding.
PI stands for Polarization Index.
It is a ratio of insulation resistance measured at 10 minutes to that measured at 1 minute.
It is used to determine the condition of the motor winding insulation.
A PI value of 2 or more indicates good insulation.
A low PI value indicates poor insulation and the motor may need to be rewound or replaced.
Top trending discussions
I applied via Company Website and was interviewed in Nov 2019. There were 3 interview rounds.
I applied via Approached by Company and was interviewed before Mar 2021. There was 1 interview round.
I applied via Company Website and was interviewed in Oct 2020. There were 4 interview rounds.
I applied via Company Website and was interviewed in Aug 2020. There were 3 interview rounds.
I applied via Naukri.com and was interviewed before Feb 2021. There were 2 interview rounds.
I applied via Recruitment Consultant and was interviewed before May 2020. There were 4 interview rounds.
I applied via Naukri.com and was interviewed before Sep 2021. There were 2 interview rounds.
All about plant, persons,
I applied via Naukri.com and was interviewed before Feb 2021. There were 3 interview rounds.
Subject expert question
based on 1 review
Rating in categories
Assistant Manager
360
salaries
| ₹4.9 L/yr - ₹18.7 L/yr |
Manager
253
salaries
| ₹8 L/yr - ₹34 L/yr |
Senior Manager
168
salaries
| ₹10 L/yr - ₹41.5 L/yr |
Deputy Manager
139
salaries
| ₹6.4 L/yr - ₹23 L/yr |
Sales Manager
118
salaries
| ₹2 L/yr - ₹9 L/yr |
UltraTech Cement
JK Cement
Grasim Industries
Shree Cement