What is interlocking in Air Circuit breaker

AnswerBot
1y

Interlocking in an Air Circuit Breaker is a mechanism that ensures the safe operation of the breaker by preventing certain actions from occurring simultaneously.

  • Interlocking is a safety feature in air...read more

Dev
2y

Machanically interlocked circuit are inteded to prohibit both power sources from being simultaneously connectev to the load

Sunil Sunny
5y
Electrical and Mechanical Interlock are used when there two or more source of power supply to a common load. For example a Power Utility Electric supply and a standby Generator power supply. Of course we do not want this two supply to be connected to the load, not unless properly synchronize, as the smaller Power supply will get motorize and eventually be burnt. Usually in the case of smaller size of Standby generator which is being normally protected by a electrical and mechanical interlocking device. Electrical interlocking device like (ACB) Air Circuit or Breaker and Mechanical Interlocking device is a mechanical way, bolt or metal strips, design so as not to switch on the two ACB power supply source at the same time. You can only switch on one breaker at a time. This will avoid the Electrical Fault cause by two power source simultaneously supplying common load. The safest way is to use both Electrical and Mechanical interlock on multi source op power supply. The main purposes for interlocking system are
  • Automatically ‘Trip’ the switching device while it is carrying over load or fault current
  • To prevent the switching mechanism from being ‘on’ position during set ‘off’ position.
  • Opening of access doors or panels before setting the switching device in its ‘off’ position.
  • To isolated the access by human operators while the system energized.
  • To avoid easy access to the bus bars when the switching devices in ON position
  • To prevent earthing switches from being closed on to live circuits or bus bars.
  • Incorrect electrical operation of a complex process system in which various external devices,motors or pumps are intimately related.
  • To avoid pump or electrical motor operate or  running other than their sequence accidentally.
Add answer anonymously...
JLL Assistant Property Manager Interview Questions
Stay ahead in your career. Get AmbitionBox app
qr-code
Helping over 1 Crore job seekers every month in choosing their right fit company
65 L+

Reviews

4 L+

Interviews

4 Cr+

Salaries

1 Cr+

Users/Month

Contribute to help millions
Get AmbitionBox app

Made with ❤️ in India. Trademarks belong to their respective owners. All rights reserved © 2024 Info Edge (India) Ltd.

Follow us
  • Youtube
  • Instagram
  • LinkedIn
  • Facebook
  • Twitter